The Fire Protection Systems
The following
‘method’ statement covers the Automatic Foam Water Sprinkler description,
installation, testing & commissioning.
Description of Dry Riser System:
Automatic Foam Water Sprinkler and Fire Alarm systems are the
basic Fire Fighting Equipments fixed / installed on the RobotPark.
Automatic Foam Water Sprinkler system comprises of
3 basic parts:
a.
Automatic Sprinkler Heads – 68
deg. C, Pendent type mounted in pairs on every car cell within the RobotPark.
b.
Premixed Set of Cylindrical Foam
Tanks.
c.
Air Compressor to maintain the
system pressure.
Fire Alarm System comprises of two basic parts:
a.
Automatic smoke detector.
b.
Fire Alarm Control Panel.
The Automatic
Foam Water Sprinkler system is designed as per NFPA-16 (Foam Water Sprinkler
System) to protect the Parking Area with high degree of protection against oil
fire. Each automatic sprinkler coverage area is 4m x 3m minimum connected via
the wet pipe. The fluid agent is a mixture solution of 3% AFFF / 97% water. The
system solution is stored in the pressure vessel where the system pressure is
maintained through an air compressor fixed adjacent to the pressure vessel.
Operation of
Automatic Foam-Water Sprinkler System:
When
unfortunate fire takes place and the heat temperature rises initially to only
68°C, the sprinkler bulb bursts to release the pressurized foam water solution
covering the protected area.
Simultaneously, the appropriate smoke detector activates an alarm signal to both
of the local control panel and remote unit/s.
Note:
The foam/water solution is released on continuous basis for nearly 6 minutes or
otherwise stopped manually through the respective valve/s.